Plan Review Notes
Plan Review Notes For Permit 04031252
Permit Number 04031252
Review Stop M
Sequence Number 1
Notes
Date Text
2004-04-05 00:00:00DENIED:
 1.PLAN SHEET 3 OF 3 A/C PLAN, DUCT
 SIZE TO ONE OF THE SUPPLY TO BEDROOM IS
 NOT SIZED (1-10" & 1-4" TO THE BATHROOM)
 IT APPEARS THE OTHER SUPPLY DUCT WOULD
 BE A 10" ALSO.PLEASE CLARIFY.
  
 2.RETURN AIR REQUIRED TO THE BEDROOM
 AREA FOR COMPLIANCE WITH 2001 FBC(M)
 601.4.PLEASE SEE THE ATTACHED SCHEDULE
 FOR PROPER SIZING.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.