Plan Review Notes For Permit 04031232 |
Permit Number |
04031232 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-12 00:00:00 | PROVISO: | | 1.RETURN AIR FROM THE MASTER BEDROOM | | SHALL BE A MINIMUM OF 15".ALL AIR INTO | | THE MASTER SUITE IS TO BE INCLUDED FOR | | THE "TOTAL" OF SUPPLY AIR FOR THAT SPACE | | REVISED 2001 FBC(M) 601.4 EXCEPTION #1 | | & 3. | | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|