Plan Review Notes
Plan Review Notes For Permit 04031232
Permit Number 04031232
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-27 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2. SPECIFY ON PLANS THE DOOR FROM THE
 GARGE TO CONDITIONED SPACE IS SOLID
 CORE OR INSULATED PER FBC 13-603.
  
 3. SPECIFY ON PLANS THE WINDOW IN BATH
 #3 WHICH IS WITHIN 3' HORIZONTALLY OF A
 TUB OR SHOWER IS TEMPERED PER FBC 2405.2
  
 4. SHOW TREAD WIDTH & RISER DETAIL ON
 PLANS. SEE FBC 1007.3.1.
  
 5. SPECIFY THE LENGTH/EMBED DEPTH OF THE
 3/16" TAPCON IN DETAIL #8ON SHEET A.
  
 6. SPECIFY THE DESIGN PRESSURES FOR THE
 WINDOWS ON SHEET 1 OF 7.
  
 ANY QUESTIONS PLEASE CALL;
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved