2004-03-31 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| FORMATION REQUIRED FOR PLAN REVIEW |
| 1) FBC-2001 SEC 424.2.6.1 ENGINEERING |
| DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| ANSI/NSPI-5. (ADD TO NOTES) |
| 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| 3) FBC-2001424.2.7.1 POOL CIRCULATING |
| PUMPS SHALL BE EQUIPPED ON THE INLET |
| SIDE WITH AN APPROVED TYPE HAIR AND LINT |
| STRAINER WHEN USED WITH A PRESSURE FIL- |
| TER. (DETAIL OR ADD TO NOTES) |
| 4) FBC-2001 424.2.7.2 PUMPS AND EQUIP- |
| MENT SHALL BE MOUNTED ON A SUBSTANTIAL |
| BASE IN A MANNER THAT WILL ELIMINATE |
| STRAIN ON PIPING. SLAB SHALL BE A NOMIN- |
| AL 4" THICK. (DETAIL) |
| 5) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| ORD. #2853-95, BACKFLOW REQUIRED ON |
| WATER SERVICE. (ADD TO NOTES) |
| 6) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| TEST SHALL BE APPROVED FOR PVC PIPE AND |
| FITTINGS. (ADD TO NOTES) |
| 7) FBC-2001 424.2.13.2JOINTS AND CON- |
| NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| NOTES) |
| 8)A PROFESSIONAL ENGINEER SHALL SIGN HIS |
| NAME AND AFFIX HIS SEAL TO ALL PLANS, |
| SPECIFICATIONS, REPORTS AND FINAL BID |
| DOCUMENTS PROVIDED TO THE OWNER OR THE |
| OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| MENTS PREPARED OR ISSUED BY SAID REGIS- |
| TRANT AND BEING FILED FOR PUBLIC RECORD. |
| THE DATE THAT THE SIGNATURE AND SEAL IS |
| AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| UNDER THE SIGNATURE OF THE PROFESSIONAL |
| ENGINEER, FAC 61G15-23.002(1) |
| FS 471.025 |
| EACH SHEET OF PLANS AND PRINTS WHICH |
| MUST BE SEALED UNDER THE PROVISIONS OF |
| CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| DATED BY THE PROFESSIONAL ENGINEER IN |
| RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| FS 471.025 |
| |