2004-03-31 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) SHT A-2 SANITARY RISER DIAGRAM DOES | | NOT MEET CODE REQUIREMENTS. | | A) MINIMUM 3" TO WATER CLOSET. TABLE | | 710.1(1) FOOTNOTE A. | | B) CLEAN OUT REQUIRED 4' ABOVE FLOOR AT | | WASHMACHINE. SECTION 708.9 | | C) STANDPIPE REQUIRED AT WASH MACHINE | | SECTIONS 1002.1 & 802.4. | | D) WASH MACHINE SHALL CONNECT BELOW | | WASTE ARM OF THE KITCHEN SINK. SECTION | | 706.3 | | 2)ENGINEERS SHALL LEGIBLY INDICATE THEIR | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | SHEET. IF PRACTICING THROUGH A DULY | | AUTHORIZED ENGINEERING BUSINESS, ENGIN- | | EERS, ENGINEERS SHALL LEGIBLY INDICATE | | THEIR NAME AND LICENSE NUMBER, AS WELL | | AS, THE NAME, ADDRESS AND CERTIFICATE OF | | AUTHORIZATION NUMBER OF THE ENGINEERING | | BUSINESS ON EACH SHEET. A TITLE BLOCK | | WILL SATISFY THIS REQUIREMENT. FAC | | 61G15-23.002(2) - FS 471.025 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|