Plan Review Notes
Plan Review Notes For Permit 04031163
Permit Number 04031163
Review Stop E
Sequence Number 1
Notes
Date Text
2004-04-02 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PANEL SCHEDULE NOTES INDICATE A
 200 AMP SERVICE. THE RISER IS LABLED
 150 AMP. PLEASE CORRELATE.
  
 2} PER 220.31 THERE IS NO DEMAND TAKEN
 FOR THE A/C. ALSO NOTE THAT THIS LOAD
 CALCULATION ALLOWS ALL BUT THE 1ST
 8000VA TO BE TAKEN @ 40%. RECALCULATE
 LOAD AND INDICATE METHOD USED. (ARTICLE
 #.)
  
 3} THE LOADS FOR THE HEAT STRIP & COND.
 UNIT ARE REVERSED ON THE SCHEDULE.
  
 4} RECEPTACLES NEED TO BE ADDED IN THE
 BEDROOM TO COMPLY WITH 210.52(A).
  
 5} PLEASE PROVIDE A PANEL SCHEDULE SO
 THAT BRANCH CIRCUIT CODE COMPLIANCE CAN
 BE DETERMINED.
  
 6} PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 8} ISLAND RECEPTACLES MUST BE GFI
 PER210.8(A)(6).
  
 9} A RECEPTACLE MUST BE ADDED AT THE
 BACK OF THE HOUSE (OUTSIDE PER
 210.52(E).
  
 10} SEE PLUMBING COMMENTS FOR TITLE
 BLOCK & SEAL REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL,
 ALSO NOTE CODE REDLINED SET OF PLANS.
  