| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} THE PANEL SCHEDULE NOTES INDICATE A |
| 200 AMP SERVICE. THE RISER IS LABLED |
| 150 AMP. PLEASE CORRELATE. |
| |
| 2} PER 220.31 THERE IS NO DEMAND TAKEN |
| FOR THE A/C. ALSO NOTE THAT THIS LOAD |
| CALCULATION ALLOWS ALL BUT THE 1ST |
| 8000VA TO BE TAKEN @ 40%. RECALCULATE |
| LOAD AND INDICATE METHOD USED. (ARTICLE |
| #.) |
| |
| 3} THE LOADS FOR THE HEAT STRIP & COND. |
| UNIT ARE REVERSED ON THE SCHEDULE. |
| |
| 4} RECEPTACLES NEED TO BE ADDED IN THE |
| BEDROOM TO COMPLY WITH 210.52(A). |
| |
| 5} PLEASE PROVIDE A PANEL SCHEDULE SO |
| THAT BRANCH CIRCUIT CODE COMPLIANCE CAN |
| BE DETERMINED. |
| |
| 6} PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| |
| 7} PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| 8} ISLAND RECEPTACLES MUST BE GFI |
| PER210.8(A)(6). |
| |
| 9} A RECEPTACLE MUST BE ADDED AT THE |
| BACK OF THE HOUSE (OUTSIDE PER |
| 210.52(E). |
| |
| 10} SEE PLUMBING COMMENTS FOR TITLE |
| BLOCK & SEAL REQUIREMENTS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL, |
| ALSO NOTE CODE REDLINED SET OF PLANS. |
| |