Plan Review Notes For Permit 04031120
Permit Number 04031120
Review Stop M
Sequence Number 1
Notes
Date Text
2004-03-23 00:00:00PROVISO:
 1.RETURN AIR REQUIRED FROM BEDROOM
 AREAS PER REVISED 2001 FBC(M) 601.4.
 SEE THE ATTACHED FOR PROPER SIZING OF
 RETURN AIR JUMPERS & TRANSFER GRILLES.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.