Plan Review Notes
Plan Review Notes For Permit 04031090
Permit Number 04031090
Review Stop E
Sequence Number 4
Notes
Date Text
2004-06-22 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS
 REVIEW. BATH RECEPT IS STILL SHOWN
 CONNECTED TO AN ADDTIONAL HALLWAY RECEPT
 PLEASE SEE 210.52D,210.11C3
 NO OTHER RECEPTS ARE PERMITTED ON THIS
 GFI CIRCUIT.
  
 THESE PLANS ARE FOR A"MASTER" AND NO
 REDLINES CAN BE DONE. PLANS MUST BE 100%
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  