Plan Review Notes
Plan Review Notes For Permit 04031090
Permit Number 04031090
Review Stop B
Sequence Number 4
Notes
Date Text
2004-06-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE COVER SHEET CONTAINS THE NAME
 OF DAVID LAWRENCE ARCHITECTURE INC.
 A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED, SEE PREVIOUS LIST.
  
 2.)SEE PREVIOUS LIST, ITEM #3.THE
 SHUTTER SCHEDULE AND KEY PLAN DO NOT
 CORRELATE WITH THE FLOOR PLAN.FOR
 INSTANCE, OPEINING D ON THE FLOOR PLAN
 IS SHOWN AS A 2'8X5'3 WINDOW; ON THE
 SHUTTER SCHEDULE IT IS OPENING 6, 78X80.
 OPENING #7 IS ALSO INCORRECT.PLEASE
 CHECK ALL OPENING SIZES.
  
 3.)SEE PREVIOUS LIST, ITEM #5.NOW
 THE STATE PRODUCT APPROVAL HAS AN
 APPROVED STATUS BUT THE TEST REPORT
 IS MISSING FOR THE MULLIONS.
  
 4.)SEE PREVIOUS LIST, ITEM #4. PROVIDE
 THE STATE PRODUCT APPROVAL FOR THE
 ODL DOOR.I WAS UNABLE TO DETERMINE
 WHICH PRODUCT APPROVAL, IF ANY, WAS THE
 CORRECT ONE ON THE FLORIDA STATE
 WEBSITE.CONTACTING THE ODL TECHNICAL
 REPRESENTATIVE, [email protected], MAY
 ASSIST IN DETERMINING THE CORRECT
 PRODUCT APPROVAL AND TEST REPORT THAT
 YOU NEED TO SUBMIT.