2004-06-23 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)THE COVER SHEET CONTAINS THE NAME |
| OF DAVID LAWRENCE ARCHITECTURE INC. |
| A CERTIFICATE OF AUTHORIZATION IS |
| REQUIRED, SEE PREVIOUS LIST. |
| |
| 2.)SEE PREVIOUS LIST, ITEM #3.THE |
| SHUTTER SCHEDULE AND KEY PLAN DO NOT |
| CORRELATE WITH THE FLOOR PLAN.FOR |
| INSTANCE, OPEINING D ON THE FLOOR PLAN |
| IS SHOWN AS A 2'8X5'3 WINDOW; ON THE |
| SHUTTER SCHEDULE IT IS OPENING 6, 78X80. |
| OPENING #7 IS ALSO INCORRECT.PLEASE |
| CHECK ALL OPENING SIZES. |
| |
| 3.)SEE PREVIOUS LIST, ITEM #5.NOW |
| THE STATE PRODUCT APPROVAL HAS AN |
| APPROVED STATUS BUT THE TEST REPORT |
| IS MISSING FOR THE MULLIONS. |
| |
| 4.)SEE PREVIOUS LIST, ITEM #4. PROVIDE |
| THE STATE PRODUCT APPROVAL FOR THE |
| ODL DOOR.I WAS UNABLE TO DETERMINE |
| WHICH PRODUCT APPROVAL, IF ANY, WAS THE |
| CORRECT ONE ON THE FLORIDA STATE |
| WEBSITE.CONTACTING THE ODL TECHNICAL |
| REPRESENTATIVE, [email protected], MAY |
| ASSIST IN DETERMINING THE CORRECT |
| PRODUCT APPROVAL AND TEST REPORT THAT |
| YOU NEED TO SUBMIT. |