Plan Review Notes
Plan Review Notes For Permit 04031090
Permit Number 04031090
Review Stop B
Sequence Number 3
Notes
Date Text
2004-06-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST.DAVID
 LAWRENCE ARCHITECTURE INC. IS REQUIRED
 TO HAVE A CERTIFICATE OF AUTHORIZATION
 (SHEET 1).PLEASE PROVIDE.MASTERS
 CANNOT BE REDLINED, SEE SHEET 9.1 TITLE
 BLOCK.
  
 2.)EMERGENCY ESCAPE SHALL BE PROVIDED
 DURING THE THREAT OF A STORM, TO BE
 PROVIDED ON THE FIRST FLOOR, FBC1005.4.5
 THE IMPACT DOOR IS ON THE SECOND FLOOR.
  
 3.)THE SHUTTER SCHEDULE AND KEY PLAN
 DO NOT CORRELATE WITH THE FLOOR PLAN.
 THE DOOR APPEARS TO BE IN THE WRONG
 LOCATION, 2ND FLOOR.EMERGENCY ESCAPE
 IS REQUIRED FBC1005.4.5.
  
 4.)DO NOT STAPLE DIFFERENT PRODUCT
 APPROVALS TOGETHER.EACH PRODUCT
 APPROVAL SHOULD INCLUDE THE FLORIDA
 STATEWIDE, LOCAL OR SITE SPECIFIC WITH
 A TEST REPORT.SEE PREVIOUS LIST IN
 REGARDS TO THE ODL DOOR, STILL NO
 STATE APPROVAL SUBMITTED.
  
 5.)THE STATE PRODUCT APPROVAL FOR
 THE MULLIONS IS PENDING.PLEASE PROVIDE
 A CURRENT (APPROVED STATUS) PRODUCT
 APPROVAL.ALSO THE DRAWINGS ARE FOR
 NORANDEX, NOT SIMONTON MULLIONS.
  
 6.)PROVIDE A TITLE BLOCK FOR THE
 ENGINEER ON THE TRUSS LAYOUT PAGE.
 SEE DESIGN CRITERIA, MASTERS CANNOT BE
 REDLINED.
  
 7.)TRUSS LOADING ON SHEET 3.1
 CONFLICTS WITH THE ENGINEERING.REVISE
 EITHER THE PLAN OR THE TRUSS ENGINEERING
 SO THAT THE TWO ARE CONSISTENT.