2004-06-04 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)SEE PREVIOUS LIST.DAVID |
| LAWRENCE ARCHITECTURE INC. IS REQUIRED |
| TO HAVE A CERTIFICATE OF AUTHORIZATION |
| (SHEET 1).PLEASE PROVIDE.MASTERS |
| CANNOT BE REDLINED, SEE SHEET 9.1 TITLE |
| BLOCK. |
| |
| 2.)EMERGENCY ESCAPE SHALL BE PROVIDED |
| DURING THE THREAT OF A STORM, TO BE |
| PROVIDED ON THE FIRST FLOOR, FBC1005.4.5 |
| THE IMPACT DOOR IS ON THE SECOND FLOOR. |
| |
| 3.)THE SHUTTER SCHEDULE AND KEY PLAN |
| DO NOT CORRELATE WITH THE FLOOR PLAN. |
| THE DOOR APPEARS TO BE IN THE WRONG |
| LOCATION, 2ND FLOOR.EMERGENCY ESCAPE |
| IS REQUIRED FBC1005.4.5. |
| |
| 4.)DO NOT STAPLE DIFFERENT PRODUCT |
| APPROVALS TOGETHER.EACH PRODUCT |
| APPROVAL SHOULD INCLUDE THE FLORIDA |
| STATEWIDE, LOCAL OR SITE SPECIFIC WITH |
| A TEST REPORT.SEE PREVIOUS LIST IN |
| REGARDS TO THE ODL DOOR, STILL NO |
| STATE APPROVAL SUBMITTED. |
| |
| 5.)THE STATE PRODUCT APPROVAL FOR |
| THE MULLIONS IS PENDING.PLEASE PROVIDE |
| A CURRENT (APPROVED STATUS) PRODUCT |
| APPROVAL.ALSO THE DRAWINGS ARE FOR |
| NORANDEX, NOT SIMONTON MULLIONS. |
| |
| 6.)PROVIDE A TITLE BLOCK FOR THE |
| ENGINEER ON THE TRUSS LAYOUT PAGE. |
| SEE DESIGN CRITERIA, MASTERS CANNOT BE |
| REDLINED. |
| |
| 7.)TRUSS LOADING ON SHEET 3.1 |
| CONFLICTS WITH THE ENGINEERING.REVISE |
| EITHER THE PLAN OR THE TRUSS ENGINEERING |
| SO THAT THE TWO ARE CONSISTENT. |