Plan Review Notes
Plan Review Notes For Permit 04031090
Permit Number 04031090
Review Stop E
Sequence Number 2
Notes
Date Text
2004-04-27 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE 40A OCP FOR OVEN ON
 #10 AWG.
  
 2)NOTE: PLEASE CORRELATE LOAD SHOWN FOR
 AHU, PANEL SCHEDULE SHOWS 11KW AND LOAD
 CALCS INDICATE 10KW. NOTE, MOST "10KW"
 HEATSTRIPS ARE ACTUALY 9.6 AND .4 FOR
 MOTOR OR THERE-ABOUTS.
 MECH PLANS SHOW OCP FOR A/C COND UNIT
 AT 25A'S.
  
 THESE PLANS ARE BEING SUBMITTED FOR
 MASTER PLANS AND CAN NOT BE REDLINED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  