Plan Review Notes For Permit 04031090 |
Permit Number |
04031090 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-04-27 00:00:00 | *** UNSAT *** | | | | 1)NOTE: PLEASE SEE 40A OCP FOR OVEN ON | | #10 AWG. | | | | 2)NOTE: PLEASE CORRELATE LOAD SHOWN FOR | | AHU, PANEL SCHEDULE SHOWS 11KW AND LOAD | | CALCS INDICATE 10KW. NOTE, MOST "10KW" | | HEATSTRIPS ARE ACTUALY 9.6 AND .4 FOR | | MOTOR OR THERE-ABOUTS. | | MECH PLANS SHOW OCP FOR A/C COND UNIT | | AT 25A'S. | | | | THESE PLANS ARE BEING SUBMITTED FOR | | MASTER PLANS AND CAN NOT BE REDLINED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|