Plan Review Notes
Plan Review Notes For Permit 04031090
Permit Number 04031090
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-25 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE CONDUCTOR SIZE FOR THE SERVICE ON
 THE RISER DIAGRAM IS UNDERSIZED PER
 210.15(B)(6). MUST BE MINIMUM #2/0.
  
 2} PLEASE SEE 250.50 FOR GROUNDING AND
 AMMEND NOTE #4 ON RISER NOTES TO
 INCLUDE COLD WATER PIPE.
  
 3} THE LOAD CALCULATION IS INCORRECT,
 PLEASE RECALCULATE PER 220.3.
  
 4} THE OVEN CALCULATION MUST COMPLY WITH
 220.19, (8 KW MIN).
  
 5} THE NEUTRAL CALCULATION IS INCORRECT
 PER 220.22, SEE REVIEWED SET OF PLANS.
  
 6} THE AMPERAGE FOR ON THE PANEL
 SCHEDULE FOR THE AHU AND THE CU. DO NOT
 CORRELATE WITH THE MECHANICAL PLANS,
 PLEASE REVISE.
  
 7} A RECEPTACLE MUST BE ADDED AT THE CU
 PER 210.63.
  
 8} A SMOKE DETECTOR MUST BE ADDED IN
 "CLOSE PROXIMITY" OF THE STAIRWELL PER
 NFPA-72, AND 905.2.2 FBC.
  
 9} THE SMOKE DETECTOR NEAR THE UPPER
 BATH #2 MUST BE A MINIMUM OF 3' AWAY
 FROM THE DOOR PER 8-1.4.2 NFPA-72.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026