Plan Review Notes For Permit 04031082 |
Permit Number |
04031082 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-04-29 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | A) FROM PREVIOUS REVIEW: THE COMMENT | | NUMBER SHALL REMAIN THE SAME TO AVOID | | CONFUSION. | | 3) UPON FURTHER REVIEW, NOW UNDERSTAND- | | ING THAT THIS A MEDICAL BUILDING, THE | | RPZ BACKFLOW IS NOT REQUIRED FOR THE | | WATER SERVICE. - SECTION 608.3-ALL | | DEVICES, APPURTENANCES, APPLIANCES AND | | APPARATUS INTENDED TO SERV SOME SPECIAL | | FUNCTION, SUCH AS STERILIZATION, DISTILL | | ATION, PROCESSING, COOLING, ECT SHALL BE | | PROVIDED WITH BACKFLOW PROTECTION. FILT- | | ERS SHALL BE PROTECTED AGAINST CONTAMIN- | | ATION. INDICATE ON PLANS OR PUT NOTE ON | | PLANS FOR THIS REQUIREMENT. (SEE COMPRE- | | SSOR ECT.) | | 5) BACKFLOW PROTECTION NOT SHOWN FOR THE | | COMPRESSOR. SEE PREVIOUS COMMENT. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|