Plan Review Notes
Plan Review Notes For Permit 04031082
Permit Number 04031082
Review Stop P
Sequence Number 2
Notes
Date Text
2004-04-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 A) FROM PREVIOUS REVIEW: THE COMMENT
 NUMBER SHALL REMAIN THE SAME TO AVOID
 CONFUSION.
 3) UPON FURTHER REVIEW, NOW UNDERSTAND-
 ING THAT THIS A MEDICAL BUILDING, THE
 RPZ BACKFLOW IS NOT REQUIRED FOR THE
 WATER SERVICE. - SECTION 608.3-ALL
 DEVICES, APPURTENANCES, APPLIANCES AND
 APPARATUS INTENDED TO SERV SOME SPECIAL
 FUNCTION, SUCH AS STERILIZATION, DISTILL
 ATION, PROCESSING, COOLING, ECT SHALL BE
 PROVIDED WITH BACKFLOW PROTECTION. FILT-
 ERS SHALL BE PROTECTED AGAINST CONTAMIN-
 ATION. INDICATE ON PLANS OR PUT NOTE ON
 PLANS FOR THIS REQUIREMENT. (SEE COMPRE-
 SSOR ECT.)
 5) BACKFLOW PROTECTION NOT SHOWN FOR THE
 COMPRESSOR. SEE PREVIOUS COMMENT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved