Plan Review Notes For Permit 04031082 |
Permit Number |
04031082 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-10 00:00:00 | DENIED: | | 1.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | 2.PLEASE INDICATE LOCATION OF THE | | CONDENSING UNIT.ROOF APPLICATIONS | | SHALL COMPLY WITH 2001 FBC 1511.7. | | | | 3.INDICATE REFRIGERANT AND CONDENSATE | | LINES.INDICATE TERMINATION OF | | CONDENSATE. | | | | 4.DUCT SMOKE DETECTORS SHALL HAVE | | NOTIFICATION TO ALARM/STROBE IN NORMALLY | | OCCUPIED AREAS PER NFPA 90A 4-4.4.3(A). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|