2004-04-10 00:00:00DENIED:
 1.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 2.PLEASE INDICATE LOCATION OF THE
 CONDENSING UNIT.ROOF APPLICATIONS
 SHALL COMPLY WITH 2001 FBC 1511.7.
  
 3.INDICATE REFRIGERANT AND CONDENSATE
 LINES.INDICATE TERMINATION OF
 CONDENSATE.
  
 4.DUCT SMOKE DETECTORS SHALL HAVE
 NOTIFICATION TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS PER NFPA 90A 4-4.4.3(A).
  