Plan Review Notes For Permit 04031079
Permit Number 04031079
Review Stop M
Sequence Number 1
Notes
Date Text
2004-03-23 00:00:00PROVISO:
 1.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 2.TRANSFER AIR GRILLES INDICATED ON
 THE PLAN ARE NOT PER THE REVISED 2001
 FBC(M) 601.4 EXCEPTION #2, 50 SQ INCHES
 OF GRILLE AREA TO 100 CFM OF SUPPLY AIR.
 10" X 10" = 100 SQ IN.PLEASE INCREASE
 TRANSFER GRILLE SIZE TO COMPLY WITH
 CODE REQUIREMENT.
  