2004-03-23 00:00:00 | PROVISO: | | 1.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | 2.TRANSFER AIR GRILLES INDICATED ON | | THE PLAN ARE NOT PER THE REVISED 2001 | | FBC(M) 601.4 EXCEPTION #2, 50 SQ INCHES | | OF GRILLE AREA TO 100 CFM OF SUPPLY AIR. | | 10" X 10" = 100 SQ IN.PLEASE INCREASE | | TRANSFER GRILLE SIZE TO COMPLY WITH | | CODE REQUIREMENT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|