2004-05-08 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE 210.52D,210.11C3
 VERIFY #12, 20A CIRCUIT(S) FOR BATH
  
 2)NOTE: PLEASE SHOW CONTROLS FOR LTS
 PER 210.70
  
 3)NOTE: PLEASE SEE FBC 104.2.1, PLANS
 MUST HAVE PRINTED NAME AND SIGNATURE
 FOR PERSON RESPONSIBLE FOR DRAWING.
 THIS IS REQD' FOR ALL PLANS WEATHER OR
 NOT COMMENT IS MADE BY OTHER REVIEWERS.
  
 **NOTE:: ORIG FILE SET OF PLANS SHOWS
 ELECTRICAL PANEL IN WHAT APPEARS TO BE
 A CLOSET WITH SHELVES INFRONT?
 PANEL IS NOT PERMITTED IN A STORAGE
 CLOSET AND ALSO MUST MEET 110.26
 408.7
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  