Plan Review Notes For Permit 04030912 |
Permit Number |
04030912 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-01 00:00:00 | PROVISO: | | 2001 FBC(M) 601.4 - | | RETURN AIR FROM THE MASTER SUITE IS NOT | | SIZED PROPERLY.RETURN AIR SHALL BE | | EQUAL TO SUPPLY FOR A "DUCTED" RETURN. | | THE MINIMUM SIZE SHALL BE 12".PLEASE | | REVISE PRIOR TO INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|