Plan Review Notes
Plan Review Notes For Permit 04030774
Permit Number 04030774
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-15 00:00:00BUILDING REVIEW PROVISO:
 1-FLOOD ZONE AO. NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.
 2-DETAIL E/4 AND RESIDENTIAL NOTES ON
 DWG #2 DON'T MATCH. CLARIFY FASTENER
 SPACING. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-TYPICAL WALL SECTION A/4: CLARIFY
 WHERE ARE TABLES 6 AND 8 FOR ROOF TILE
 FASTENER TAKEN FROM. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.