Plan Review Notes
Plan Review Notes For Permit 04030748
Permit Number 04030748
Review Stop B
Sequence Number 2
Notes
Date Text
2004-04-22 00:00:00BUILDING REVIEW PROVISO:
 1-DETAIL E/4 AND RESIDENTIAL NOTES ON
 DWG #2 DON'T MATCH. CLARIFY SPACING
 OF FASTENERS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 2-TYPICAL WALL SECTION A/4:SPECIFY WHERE
 ARE TABLES 6 AND 8 FOR ROOF TILE
 FASTENING TAKEN FROM. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 3-FLOOD ZONE AO: NEED TO PROVIDE THE
 ELEVATION CERTIFICATE.