2004-05-05 00:00:00********* REDLINED/ PROVISO ***********
  
 1)NOTE; PLEASE SEE MAX LOAD FOR 1P20A
 IS 1.9KW. IRRG PUMP AND WASHER SHOWN AT
 2KW?
  
 2)NOTE: PLEASE SEE 220.19, MIN LOAD TO
 BE SHOWN FOR RANGE IS 8KW. SHOWN AS 7.5
  
 SD'S REDLINED TO BE INSTALLED PER NFPA-
 -72 8-1.4.2
  
 REVISE PLANS BEFORE ROUGH.
  