Plan Review Notes For Permit 04030742 |
Permit Number |
04030742 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-05-05 00:00:00 | ********* REDLINED/ PROVISO *********** | | | | 1)NOTE; PLEASE SEE MAX LOAD FOR 1P20A | | IS 1.9KW. IRRG PUMP AND WASHER SHOWN AT | | 2KW? | | | | 2)NOTE: PLEASE SEE 220.19, MIN LOAD TO | | BE SHOWN FOR RANGE IS 8KW. SHOWN AS 7.5 | | | | SD'S REDLINED TO BE INSTALLED PER NFPA- | | -72 8-1.4.2 | | | | REVISE PLANS BEFORE ROUGH. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|