Plan Review Notes
Plan Review Notes For Permit 04030625
Permit Number 04030625
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-03-16 00:00:00************DENIED**********************
 1) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 2) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 APPROVAL OF THESE PLANS.
  
 3) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
 4) ALL DUCT DETECTORS SHALL SEND AND PUT
 THE SYSTEM IN GENERAL FIRE ALARM MODE IN
 THE CITY OF WEST PALM BEACH NOT A
 SUPERVISORY SIGNAL.
  
 THESE COMMENTS AND NOTES ARE FOR PERMITS
 # 04030625 AND 04030626
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910