2004-04-14 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE FL PRODUCT APPROVAL #S LISTED FOR |
| TWO OF THE FIXED GLASS WINDOWS IN THE |
| SCHEDULE ON SHEET 3 ARE INCORRECT. |
| |
| 3) SPECIFY THE CONNECTORS AT THE BASE OF |
| THE TWO 3-2X4 POSTS IN THE WALL BELOW |
| THE GIRDER TRUSS AT MASTER SUITE. |
| |
| 4) SPECIFY THE ATTIC LIVE LOAD ON THE |
| PLANS. SEE FBC TABLE 1604.1. |
| |
| 5) SUBMIT STATE PRODUCT APPROVAL FOR THE |
| COLLIER GARAGE DOOR WITH APPROVED STATUS |
| AND FOR THE 8'X 7' GARAGE DOOR WHICH IS |
| SMALLER THAN THE MINIMUM SIZE ALLOWED BY |
| THE PROD.APP. DRAWING. |
| |
| 6) THE TRUSS ANCHOR SCHEDULE ON SHEET 9 |
| LISTS A NUE-VUE NVSTA 48 CONNECTOR. THE |
| STATE PRODUCT APPROVAL SUBMITTED LISTS A |
| NVRT 48 OR NVSTA 22. PLEASE CLARIFY. |
| |
| 7) THE TRUSS CONNECTOR SCHEDULE LISTS A |
| SIMPSON HUC 412 CONNECTOR WITH 1505# OF |
| UPLIFT. THE STATE PRODUCT APPROVAL IS |
| FOR A HU 412 WITH 905# OF UPLIFT. PLEASE |
| CLARIFY. |
| |
| 8) THE STORM PANEL INSTALLATION SCHEDULE |
| AND KEY PLAN IS MISSING THE WINDOW IN |
| BATH #2. PLEASE CORRECT. |
| |
| 9) THE SUBMITTAL FOR THE BUTT GLASS |
| WINDOW IS INCOMPLETE AND HAS ERRORS. THE |
| THIRD PARTY QUALITY ASSURANCE IS |
| REQUIRED. SPECIFY THE DESIGN PRESSURES. |
| LIST LIMITATIONS. SUBMIT CALCULATIONS. |
| SUBMIT THE SPECIFICATIONS FOR THE GE |
| 1200 SILICONE. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |