Plan Review Notes
Plan Review Notes For Permit 04030573
Permit Number 04030573
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-15 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE TOTAL SQUARE FEET OF A/C AREA ON
 THE PLANS IS INCORRECT ON SHEET 3.
 PLEASE CORRECT.
  
 3) THE FLORIDA PRODUCT APPROVAL NUMBERS
 LISTED FOR TWO OF THE FIXED GLASS
 WINDOWS IN THE SCHEDULE ON SHEET 3 ARE
 INCORRECT.
  
 4) PLEASE CLARIFY THE TP4X CONNECTOR
 SPECIFIED ON SHEET 2 FOR THE 3-2X4 POST
 IN THE WALL BELOW THE GIRDER TRUSS AT
 THE MASTER SUITE.
  
 5) SPECIFY THE ATTIC LIVE LOAD ON THE
 PLANS. SEE FBC TABLE 1604.1.
  
 6) SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO THE CONDITIONED SPACE
 IS REQUIRED TO BE SOLID CORE OR
 INSULATED PER FBC 13-603.
  
 7) THE TRUSS ANCHOR SCHEDULE ON SHEET 9
 LISTS A NU-VUE NVSTA 48 CONNECTOR. THE
 STATE PRODUCT APPROVAL SUBMITTED IS FOR
 A NVRT 48 CONNECTOR. PLEASE CLARIFY.
  
 8) THE TRUSS CONNECTOR SCHEDULE LISTS A
 SIMPSON HUC 412 CONNECTOR AND THE STATE
 PRODUCT APPROVAL SUBMITTED IS FOR A
 HU 412. PLEASE CLARIFY.
  
 9) SUBMIT STATE PRODUCT APPROVAL WITH
 APPROVED STATUS FOR THE COLLIER GARAGE
 DOOR AND FOR THE 8'X7' GARAGE DOOR,
 WHICH IS SMALLER THAN THE MINIMUM
 ALLOWED BY THE PROD. APP. DRAWING.
  
 10) THE SUBMITTAL FOR THE BUTT GLASS
 WINDOW IS INCOMPLETE AND HAS ERRORS.
 THE THIRD PARTY QUALITY ASSURANCE IS
 REQUIRED. THE DIMENSIONS OF THE PANELS
 NEED TO MATCH THE ARCHITECTURAL PLANS.
 THE LOT NUMBER ON SHEET 1 OF 2 IS WRONG.
 THE DESIGN PRESSURES ARE NOT GIVEN.
 SUBMIT THE CALCULATIONS. SUBMIT THE
 SPECIFICATIONS FOR THE GE 1200 SILICONE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714