 UNSAT
 ~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THE TOTAL AMPS IN THE LOAD
 CALCULATION IS 380 AMPS (SHEET E-3),
 THE SERVICE CONDUCTOR SIZE ON SHEET E-2
 IS 400 MCM WHICH PER TABLE 310.16 @ 335
 AMPS, IS NOT RATED FOR THE LOAD SERVED.
  
 2} THE"#4/OG" CONDUCTOR LISTED ON THE
 RISER SHEET E-2, BEING RAN WITH THE
 FEEDER IS INCORRECT PER 250.122 IF IT
 IS SUPPOSED TO BE THE EQUIPMENT GROUND.
  
 3} THE TOTAL KW AS COMPUTED ACROSS FOR
 L2N,N2NA & N2N DOES NOT SEEM TO ADD
 CORRECTLY, PLEASE CHECK.SHEET E-3.
  
 4} CONTINUOUS LOADS SUCH AS LIGHTING
 MUST BE CALCULATED PER 210.19(A),
 210.20(A) AND 215.2(A). PLEASE ADDRESS
 THIS IN THE CALCULATIONS.
  
 5} PLEASE INDICATE THE LIGHTING BRANCH
 CIRCUIT NUMBERS AND THE CIRCUITING FOR
 THE LIGHTS ON SHEET E-1.
  
 6} PLEASE REFER TO NOTE #10 ON SHEET
 E-3. THE REVERENCE TO ARTICLE 380-8(B),
 IS A 1999 CODE REVERENCE. PLEASAE BE
 ADVISED THAT WEST PALM BEACH HAS
 ADOPTED THE 2002 NEC. SEE ARTICLE
 404.8(B).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  