2004-03-23 00:00:00 | |
| UNSAT |
| ~~~~~ |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PLEASE SEE THE TOTAL AMPS IN THE LOAD |
| CALCULATION IS 380 AMPS (SHEET E-3), |
| THE SERVICE CONDUCTOR SIZE ON SHEET E-2 |
| IS 400 MCM WHICH PER TABLE 310.16 @ 335 |
| AMPS, IS NOT RATED FOR THE LOAD SERVED. |
| |
| 2} THE"#4/OG" CONDUCTOR LISTED ON THE |
| RISER SHEET E-2, BEING RAN WITH THE |
| FEEDER IS INCORRECT PER 250.122 IF IT |
| IS SUPPOSED TO BE THE EQUIPMENT GROUND. |
| |
| 3} THE TOTAL KW AS COMPUTED ACROSS FOR |
| L2N,N2NA & N2N DOES NOT SEEM TO ADD |
| CORRECTLY, PLEASE CHECK.SHEET E-3. |
| |
| 4} CONTINUOUS LOADS SUCH AS LIGHTING |
| MUST BE CALCULATED PER 210.19(A), |
| 210.20(A) AND 215.2(A). PLEASE ADDRESS |
| THIS IN THE CALCULATIONS. |
| |
| 5} PLEASE INDICATE THE LIGHTING BRANCH |
| CIRCUIT NUMBERS AND THE CIRCUITING FOR |
| THE LIGHTS ON SHEET E-1. |
| |
| 6} PLEASE REFER TO NOTE #10 ON SHEET |
| E-3. THE REVERENCE TO ARTICLE 380-8(B), |
| IS A 1999 CODE REVERENCE. PLEASAE BE |
| ADVISED THAT WEST PALM BEACH HAS |
| ADOPTED THE 2002 NEC. SEE ARTICLE |
| 404.8(B). |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |