2004-10-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030467
 ADD: 4500 S DIXIE HWY
 CONT: ANDERSON MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION: 2ND REVIEW
 ACTION: DENIED
  
 1) REVISION FOR BAR JOIST AND SHORING.
 SHORING DETAILS OK.
 2) REVISION FOR THE MEZZANINE BAR JOIST.
 ENGINEER TO PROVIDE WHAT THE CALCULATED
 FLOOR LOAD TO BE FOR AISLES AND SEATING
 AREAS AS BEFORE, PROVIDE LIVE AND DEAD
 LOADS. USE 100LBS FOR ISLES AND 50 LBS
 FOR SEATING AREA. GLASS HANDRAIL @ 3/4"
 THICK, 3/4" GLASS 24LBS/ SQ FTX3.5=
 84LBS/ LINEAL FT.
 3) THE CALCULATIONS FOR THE NEW STEEL
 BEAM SHEET# 1, THE SHEET IS BLANK AS FAR
 AS:
 1) DEAD LOADS
 2) LIVE LOADS
 3) COMBINED DEAD AND LIVE LOADS
  
 4) THE ENGINEER OF RECORD DOES NOT SHOW
 THAT THE NEW BAR JOIST HAS BEEN REVIEWED
 BY THEIR FIRM AND APPROVED, REVIEWED
 WITH NO EXCEPTIONS, REVISE OR DENIED.
  
 NOTE PROVIDE (3) COPIES OF ALL DOCUMENTS
 SUBMITTED.
  