Date |
Text |
2004-08-23 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04030467 |
| ADD: 4500 S DIXIE HWY |
| CONT: ANDERSON MOORE |
| TEL: (561)662-1819 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| REVISION# 3 |
| ACTION: DENIED |
| |
| 1) THRESHOLD BUILDING: ALL DOCUMENTS |
| SUBMITTED TO THE BUILDING DEPARTMENT FOR |
| A THRESHOLD BUILDING REQUIRE (3) SETS, |
| ONLY (2) WERE SUBMITTED. |
| |
| 2) SHEET S-8- CONCERNS WITH DETAIL SEC- |
| TION DETAIL "V". THRESHOLD INSPECTOR |
| JOE WAGNER HAS ADDRESSED HIS CONCRNS |
| ABOUT THE DOUBLE BAR JOIST AT THE NEW |
| EXTENSION OF THE MEZZANINE. PLEASE PRO- |
| VIDE DETAILS AS HOW THESE MEMBERS WILL |
| WORK AS A SINGLE BEAM AND NOT AS INDIVID |
| UAL MEMBERS. |
| A SECOND CONCERN IS THE GLASS GUARD- |
| RAIL, THE BAR JOIST, IF THE (GIRDER) IS |
| NOT FUSED TO MAKE A SINGLE MEMBER THE |
| WEIGHT OF THE HAND RAIL WILL BE ON THE |
| OUTSIDE BAR JOIST WHICH WILL BE CARRYING |
| A HEAVIER LOAD. |
| THE ORIGINAL PLANS DO INDICATE A FLOOR |
| LOAD OF 50 LBS LIVE LOAD WHICH IS IN |
| LINE WITH TABLE 1604.1. THE ISSUE OF |
| LIVE LOAD FOR THE AISLES HAS NOT. THE |
| SAME TABLE 1604.1. ESTABLISHES A 100 LBS |
| LIVE LOAD FOR EXIT AISLES. PROVIDE CALCU |
| LATIONS FOR THE FRONT MEZANINE AISLES |
| AND FOR THE SECONARY AISLES THAT SERVICE |
| THE MEZANINE SEATING AREA. |
| |
| 3) THE NEXT CONCERN IS THE NEW COLUMN & |
| LINTEL AT THE FOOT OF THE STAIRS. S-10 |
| INDICATES NEW COLUMNS ONTO THE EXISTING |
| FOUDATION AND STEM WALL. DOES THE EXIST- |
| ING FOUDATION DESIGN PROVIDE ENOUGH |
| BEARING STRENGTH FOR THE POINT LOADING. |
| THE OTHER CONCERN IS TO "FILL CELLS |
| (3 MIN) WITH CONCRETE". DOES THIS NOTA- |
| TION MEAN 3 CELLS VERTICALLY OR HORIZON- |
| TALLY? AT WHAT PSI? PROVIDE 4-5/8" DIA. |
| ANCHOR BOLTS? LENGHT. |
| THE NEXT ISSUE IS THE LINTEL DETAIL |
| AT THE SAME COLUMN. THE 4"X4" STEEL |
| ANGLE SHOWS A ANGLE AT THE EXISTING COL- |
| UMN WHERE THE ANGLE CAN'T CONTINUE INTO |
| THE BLOCK TO GET A SEAT. NO INFORMATION |
| HAS BEEN PROVIDED FOR ANCHORING INTO THE |
| EXISTING COLUMN. SINCE THIS IS A EXTER- |
| IOR MASONARY WALL HAS UPLIFT BEEN ADD- |
| RESSED. |
| |
| 4) STRUCTURAL PLANS S-6 INDICATE THE USE |
| OF TIMBER PURLINS, NO SIZE PROVIDED ONLY |
| THE NOTE SEE PLANS, WHERE? |
| |
| 5)S-2 PLANS INDICATE B-1 TO BE A 24"X18" |
| BUT THE INSPECTOR INDICATED THE BEAM HAS |
| BEEN REDUCED BY 10", IS THERE ADDITIONAL |
| STEEL OR A REPOSITIONING OF STEEL? |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |