Plan Review Notes
Plan Review Notes For Permit 04030467
Permit Number 04030467
Review Stop E
Sequence Number 2
Notes
Date Text
2004-05-28 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE ONE-LINE RISER DIA-
 -GRAM DOES NOT APPEAR TO SHOW ANY WIRE
 / CONDUITS SIZES TO PANELS,CL1,CL2,CL3,
 AND CL4.
 PLEASE SEE CORRELATE PANEL SCHEDULES
 WITH RISER. RISER SHOWS EACH OF THESE
 AS 225A/42 CIR PANELS, HOWEVER PANEL
 SCHEDULES SHOWS THEM AS 125A/ 42CIR
 PANELS. PLEASE SEE THAT 125A PANELS
 ARE NOT MADE AS 42 CIR. PANEL CL3 SEEMS
 TO BE THE ONLY ONE SHOWN AS 225A.
 215.5
  
 2)NOTE: PLEASE SHOW NEW PANEL CL4 BOND
 TO NEW PAVILLION FOOTER STEEL. 250.50
  
 3)NOTE: PLEASE PROVIDE FULL LEGAL
 SIGNATURE. APPEARS TO SHOW AN INITIAL
 FOR FIRST NAME. IF THIS IS THE LEGAL
 SIGNATURE, PLEASE PROVIDE A SIGNED,DATED
 AND SEALED NOTARIZED LETTER STATING THIS
 WE CAN PLACE THIS IN A FILE WE HAVE FOR
 FUTURE REFERENCE.
 PLEASE SEE FS 471.025/FAC 61G15-23.002
 WHICH REQ'S A "SIGNATURE". ALSO PER
 FBPE'S.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CONTACT ME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  