Date |
Text |
2004-05-28 00:00:00 | ********* UNSAT ********* |
| |
| 1)NOTE: PLEASE SEE ONE-LINE RISER DIA- |
| -GRAM DOES NOT APPEAR TO SHOW ANY WIRE |
| / CONDUITS SIZES TO PANELS,CL1,CL2,CL3, |
| AND CL4. |
| PLEASE SEE CORRELATE PANEL SCHEDULES |
| WITH RISER. RISER SHOWS EACH OF THESE |
| AS 225A/42 CIR PANELS, HOWEVER PANEL |
| SCHEDULES SHOWS THEM AS 125A/ 42CIR |
| PANELS. PLEASE SEE THAT 125A PANELS |
| ARE NOT MADE AS 42 CIR. PANEL CL3 SEEMS |
| TO BE THE ONLY ONE SHOWN AS 225A. |
| 215.5 |
| |
| 2)NOTE: PLEASE SHOW NEW PANEL CL4 BOND |
| TO NEW PAVILLION FOOTER STEEL. 250.50 |
| |
| 3)NOTE: PLEASE PROVIDE FULL LEGAL |
| SIGNATURE. APPEARS TO SHOW AN INITIAL |
| FOR FIRST NAME. IF THIS IS THE LEGAL |
| SIGNATURE, PLEASE PROVIDE A SIGNED,DATED |
| AND SEALED NOTARIZED LETTER STATING THIS |
| WE CAN PLACE THIS IN A FILE WE HAVE FOR |
| FUTURE REFERENCE. |
| PLEASE SEE FS 471.025/FAC 61G15-23.002 |
| WHICH REQ'S A "SIGNATURE". ALSO PER |
| FBPE'S. |
| IF THERE ARE ANY QUESTIONS, PLEASE DO |
| NOT HESITATE TO CONTACT ME. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |