Plan Review Notes For Permit 04030467 |
Permit Number |
04030467 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-03-22 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SHT P-1.0 ALL CAPPED PLUMBING PIPING | | SHALL BE INSPECTED PRIOR TO COVERING. | | 2) SHT P-2.0 FOUNTAIN PIPING, SANITARY | | PIPING SHOWS 2" @ 1/8" PER FT FALL. SEE | | PLUMBING SYSTEM INSTALLATION NOTES #3 ON | | SHT P-0.1 AND TABLE 704.1. MINIMUM 1/4" | | PER FT FAL REQUIRED. | | 3) SHT P-2.0 WATER LINE TO FOUNTAIN | | SHALL HAVE BACKFLOW PROTECTION. SECTION | | 608.13 | | 4) SHT P-3.1 WATER RISER DOES NOT SHOW | | 3/4" LINE TO FUTURE FOUNTAIN. | | 5) SHT P-3.1 WATER HAMMER ARRESTORS | | SHALL BE LOCATED NEAR THE FIXTURES IN AN | | "EFFECTIVE RANGE" NOT IN THE CEILING AS | | SHOWN. PDI-WH 201, AND MANUF. INSTALL. | | INSTRUCTIONS. | | 6) SHT P-6.0 HOSE BIBB DETAIL, AIR | | CHAMBERS ARE NOT APPROVED, DELETE FROM | | DETAIL. SECTION 604.9 - IF WATER HAMMER | | ARRESTOR IS USED, SEE COMMENT #5 FOR | | LOCATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|