Plan Review Notes
Plan Review Notes For Permit 04030467
Permit Number 04030467
Review Stop P
Sequence Number 1
Notes
Date Text
2004-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-1.0 ALL CAPPED PLUMBING PIPING
 SHALL BE INSPECTED PRIOR TO COVERING.
 2) SHT P-2.0 FOUNTAIN PIPING, SANITARY
 PIPING SHOWS 2" @ 1/8" PER FT FALL. SEE
 PLUMBING SYSTEM INSTALLATION NOTES #3 ON
 SHT P-0.1 AND TABLE 704.1. MINIMUM 1/4"
 PER FT FAL REQUIRED.
 3) SHT P-2.0 WATER LINE TO FOUNTAIN
 SHALL HAVE BACKFLOW PROTECTION. SECTION
 608.13
 4) SHT P-3.1 WATER RISER DOES NOT SHOW
 3/4" LINE TO FUTURE FOUNTAIN.
 5) SHT P-3.1 WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201, AND MANUF. INSTALL.
 INSTRUCTIONS.
 6) SHT P-6.0 HOSE BIBB DETAIL, AIR
 CHAMBERS ARE NOT APPROVED, DELETE FROM
 DETAIL. SECTION 604.9 - IF WATER HAMMER
 ARRESTOR IS USED, SEE COMMENT #5 FOR
 LOCATION.
  