Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-03-09 00:00:001) ALL NEW REQUIRED STAIRS AND RAMPS
 SHALL BE PROVIDED WITH HANDRAILS.
  
 2) PANIC HARDWARE REQUIRED AT ALL
 DOORS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS.
  
 3) SINCE THE BUILDING IS NOT FIRE
 SPRINKLER PROTECTED, ALL ELECTRICAL,
 MECHANICAL, AND SERVICE ROOMS SHALL
 BE ONE HOUR RATED WITH 45 MINUTE
 OPENING PROTECTIVES.
  
 4) SOME STAIRS ON PAGE A-2.0 ARE
 ABSENT OF HANDRAILS.
  
 5) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 6) EXITS SHALL REMAIN CLEAR.
  
 7) DEBRIS SHALL BE REMOVED DAILY
 FROM INSIDE THE BUILDING.
  
 8) BUILDING ADDRESS REQUIRED. A MINIMUM
 6" NUMBERS ARE REQUIRED.
  
 9) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL
 HANDRAILS AND GUARDRAILS.
  
 10) GASOLINE POWERED EQUIPMENT USED
 DURING DEMOLITION ACTIVITIES SHALL
 BE PROVIDED WITH ADEQUATE VENTILATION
 TO PREVENT THE ACCUMULATION OF
 CARBON MONOXIDE.
  
 11) PLEASE FURTHER DEFINE EXISTING
 EMERGENCY LIGHTS AND EXIT SIGNS IN
 SACRISITY 002, AND ALTAR 001.
  
 12) NO EMERGENCY LIGHTS IN PAVILLION
 100.
  
 13) PLEASE PROVIDE DETAILS ABOUT THE
 REQUIRED FIRE ALARM SYSTEM. THE
 PROPOSED OCCUPANT LOAD EXCEEDS 300
 PERSONS, SO A FIRE ALARM SYSTEM IS
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL