Plan Review Notes
Plan Review Notes For Permit 04030335
Permit Number 04030335
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-13 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO CONDITIONED SPACE IS
 REQUIRED TO BE SOLID CORE OR INSULATED.
 SEE FBC 13-603.
  
 3) SPECIFY ON THE PLANS THAT THE WINDOW
 IN BATH #3 WHICH IS WITHIN 3 FEET
 HORIZONTALLY OF A TUB OR SHOWER IS
 REQUIRED TO BE TEMPERED. SEE FBC 2405.2.
  
 4) THE FRONT WALL IS MISSING FROM THE
 FLOOR PLAN ON SHEET 4.
  
 5) EGRESS WINDOWS ARE REQUIRED IN THE
 MASTER BEDROOM AND BEDROOM #3. SEE FBC
 1005.4.
  
 6) SPECIFY THE MATERIAL TO BE USED FOR
 THE DRAFTSTOPPING OF THE FLOOR/CEILING
 ASSEMBLY SEPARATING IT INTO 500 SQFT
 AREAS. INDICATE THEIR APPROXIMATE
 LOCATIONS ON THE FLOOR FRAMING LAYOUT ON
 SHEET 4.
  
 7) SPECIFY THE TREAD WIDTH AND RISER
 HEIGHT ON THE PLANS. SEE FBC 1007.3.1.
  
 8) DETAIL 1 ON SHEET 6 REFERS TO FBC
 2605.5. THIS CODE SECTION DOES NOT EXIST
 PLEASE CORRECT.
  
 9) SPECIFY THE ATTIC LIVE LOAD ON THE
 PLANS. SEE FBC TABLE 1604.1.
  
 10) SPECIFY THE LENGTH/EMBED DEPTH OF
 THE 3/16" TAPCONS IN DETAIL 8 ON SHEET A
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714