Plan Review Notes
Plan Review Notes For Permit 04030308
Permit Number 04030308
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-12 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE ATTIC LIVE LOAD ON THE
 PLANS. SEE FBC TABLE 1604.1.
  
 3) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 3/16" TAPCONS IN DETAIL 8 ON SHEET A.
  
 4) SPECIFY A SOLID CORE OR INSULATED
 DOOR BETWEEN THE GARAGE AND CONDITIONED
 SPACE AS REQUIRED BY FBC 13-603.
  
 5) SITE SPECIFIC PRODUCT APPROVAL FOR
 THE BUTT GLASS WINDOW IS INCOMPLETE.
 SPECIFY QUALITY ASSURANCE. SPECIFY THE
 DESIGN PRESSURES. CORRECT THE LOT NUMBER
 LISTED ON SHEET 1 OF 2. SUBMIT THE SPECS
 FOR THE GE 1200 SILICONE. SUBMIT ALL
 CALCULATIONS. THE DIMENSIONS ON THE
 DRAWINGS ARE REQUIRED TO MATCH THOSE ON
 THE ARCHITECTURAL PLANS.
  
 6) SUBMIT LOCAL/STATE PRODUCT APPROVAL
 FOR THE SINGLE OUTSWING DOOR AT BATH #2.
  
 7) SUBMIT STATE PRODUCT APPROVAL FOR THE
 COLLIER GARAGE DOOR WITH APPROVED STATUS
 AND FOR THE 8'X7' OVERHEAD GARAGE DOOR.
  
 MAKE CORRECTIONS REQUIRED BY OTHER
 TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714