Plan Review Notes For Permit 04030308 |
Permit Number |
04030308 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-12 00:00:00 | DENIED | | | | 1) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) SPECIFY THE ATTIC LIVE LOAD ON THE | | PLANS. SEE FBC TABLE 1604.1. | | | | 3) SPECIFY THE LENGTH/EMBED DEPTH OF THE | | 3/16" TAPCONS IN DETAIL 8 ON SHEET A. | | | | 4) SPECIFY A SOLID CORE OR INSULATED | | DOOR BETWEEN THE GARAGE AND CONDITIONED | | SPACE AS REQUIRED BY FBC 13-603. | | | | 5) SITE SPECIFIC PRODUCT APPROVAL FOR | | THE BUTT GLASS WINDOW IS INCOMPLETE. | | SPECIFY QUALITY ASSURANCE. SPECIFY THE | | DESIGN PRESSURES. CORRECT THE LOT NUMBER | | LISTED ON SHEET 1 OF 2. SUBMIT THE SPECS | | FOR THE GE 1200 SILICONE. SUBMIT ALL | | CALCULATIONS. THE DIMENSIONS ON THE | | DRAWINGS ARE REQUIRED TO MATCH THOSE ON | | THE ARCHITECTURAL PLANS. | | | | 6) SUBMIT LOCAL/STATE PRODUCT APPROVAL | | FOR THE SINGLE OUTSWING DOOR AT BATH #2. | | | | 7) SUBMIT STATE PRODUCT APPROVAL FOR THE | | COLLIER GARAGE DOOR WITH APPROVED STATUS | | AND FOR THE 8'X7' OVERHEAD GARAGE DOOR. | | | | MAKE CORRECTIONS REQUIRED BY OTHER | | TRADES. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|