2004-12-09 00:00:00DENIED:
 1.ENERGY CALCULATIONS INDICATE 13 SEER
 EQUIPMENT WHEREAS THE EQUIPMENT SCHEDULE
 ON PLAN SHEET M-1 SHOWS ONLY A 12 SEER.
 PLEASE CORRELATE PLANS WITH THE ENERGY
 CALCS.
  
 2.PLEASE NOTE THE EQUIPMENT SCHEDULE
 THE SENSIBLE/LATENT BTU'S ARE SHOWN
 UNDER THE WRONG EQUIPMENT.5 TON
 INDICATES 13,800 SENS BTU'S & 5,000
 LATENT BTU'S.
  