2005-05-19 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1] SHOW THE METER LOCATION ON THE PLAN. |
| |
| 2} PANEL "A" MOVED FROM ORIGINAL |
| LOCATION. IF THE FEED WAS CHANGED FROM |
| OVERHEAD TO UNDERGROUND, INDICATE |
| DISCONNECTING MEANS REQUIRED PER 230.70, |
| CITY AMMENDMENTS. CALL ME WITH ANY |
| QUESTIONS REGARDING THIS ISSUE. |
| |
| 3} THE A/C SYSTEM ON THE PANEL SCHEDULE |
| AND IN THE LOAD CALCULATION DO NOT |
| CORRELATE WITH THE ORIGINAL, UNREVISED, |
| MECHANICAL DRAWINGS. PLEASE CORRELATE |
| THE TWO PLANS TO INDICATE ACTUAL |
| INSTALLATION. |
| |
| 4} THE OCP FOR CIRCUIT #30, BATH GFI, |
| DOES NOT COMPLY WITH 210.52(C)(3), 20 |
| AMP. |
| |
| 4} CIRCUIT #32, SAME COMMENT, ARTICLE |
| 210.52(B)(1). PANEL "A". |
| |
| 5} SEVERAL RECEPTACLES THAT WERE ON THE |
| REVIEWED PLANS HAVE BEEN REMOVED FROM |
| THIS PLAN, AND THE ROOMS THIS OCCURRED |
| IN DO NOT COMPLY WITH WITH 210.52. |
| SEE THE PLANS REVIEWED THIS SUBMITTAL |
| FOR REDLINED LOCATIONS. PLEASE CHECK FOR |
| ACTUAL PLACEMENTS FOR "AS BUILTS". |
| |
| CALL WITH QUESTIONS REGARDING COMMENTS |
| OR CODE REQUIREMENTS. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |
| [email protected] |
| FAX/:561/659-8026 |
| |
| |
| |