Plan Review Notes For Permit 04030148
Permit Number 04030148
Review Stop E
Sequence Number 3
Notes
Date Text
2005-05-19 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1] SHOW THE METER LOCATION ON THE PLAN.
  
 2} PANEL "A" MOVED FROM ORIGINAL
 LOCATION. IF THE FEED WAS CHANGED FROM
 OVERHEAD TO UNDERGROUND, INDICATE
 DISCONNECTING MEANS REQUIRED PER 230.70,
 CITY AMMENDMENTS. CALL ME WITH ANY
 QUESTIONS REGARDING THIS ISSUE.
  
 3} THE A/C SYSTEM ON THE PANEL SCHEDULE
 AND IN THE LOAD CALCULATION DO NOT
 CORRELATE WITH THE ORIGINAL, UNREVISED,
 MECHANICAL DRAWINGS. PLEASE CORRELATE
 THE TWO PLANS TO INDICATE ACTUAL
 INSTALLATION.
  
 4} THE OCP FOR CIRCUIT #30, BATH GFI,
 DOES NOT COMPLY WITH 210.52(C)(3), 20
 AMP.
  
 4} CIRCUIT #32, SAME COMMENT, ARTICLE
 210.52(B)(1). PANEL "A".
  
 5} SEVERAL RECEPTACLES THAT WERE ON THE
 REVIEWED PLANS HAVE BEEN REMOVED FROM
 THIS PLAN, AND THE ROOMS THIS OCCURRED
 IN DO NOT COMPLY WITH WITH 210.52.
 SEE THE PLANS REVIEWED THIS SUBMITTAL
 FOR REDLINED LOCATIONS. PLEASE CHECK FOR
 ACTUAL PLACEMENTS FOR "AS BUILTS".
  
 CALL WITH QUESTIONS REGARDING COMMENTS
 OR CODE REQUIREMENTS.
  