Text |
2004-04-01 00:00:00 | DENIED: | | 1.RETURN AIR REQUIRED FROM DEN/STUDY | | AREA.2001 FBC(M) 601.4. | | | | 2.SUPPLY DUCT TO THE MASTER BATH AREA | | (AHU#2) DOES NOT INDICATE SIZE. | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | 4.PROVIDE INFORMATION/CALCULATION FOR | | COMBUSTION AIR FOR THE GAS DRYER. 2001 | | FBC(M) CHAPTER 7 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|