Plan Review Notes
Plan Review Notes For Permit 04030148
Permit Number 04030148
Review Stop M
Sequence Number 1
Notes
Date Text
2004-04-01 00:00:00DENIED:
 1.RETURN AIR REQUIRED FROM DEN/STUDY
 AREA.2001 FBC(M) 601.4.
  
 2.SUPPLY DUCT TO THE MASTER BATH AREA
 (AHU#2) DOES NOT INDICATE SIZE.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 4.PROVIDE INFORMATION/CALCULATION FOR
 COMBUSTION AIR FOR THE GAS DRYER. 2001
 FBC(M) CHAPTER 7
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.