Plan Review Notes
Plan Review Notes For Permit 04030148
Permit Number 04030148
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-15 00:00:00DENIED
  
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.FBC 11-4.23.2 EXCEPTIONSAT LEAST
 ONE BATHROOM DOOR SHALL HAVE A 29 INCH
 CLEAR OPENING.
  
 4.GENERAL ARCH. NOTES #8ALL WINDOWS
 ARE TO BE IMPACT RESISTANT.THIS
 CONFLICTS WITH OTHER NOTES OF
 IMPACT PROTECTION REQUIRED.
  
 5.SUBMIT MANUFACTURER SPECIFICATIONS
 AND UL LISTING INFORMATION FOR GAS
 BBQ AND HOOD.
  
 6.SUBMIT 2 COPIES OF PRODUCT APPROVAL
 FOR 1 HR GLASS BLOCK.
  
 7.BUTT GLASS NOT USED.REMOVE
 PRODUCT APPROVAL FROM THIS APPLICATION.
  
 8.REMOVE ROOFING PRODUCT APPROVALS
 A SEPERATE ROOFING PERMIT IS REQUIRED
 SINCE A ROOFING CONTRACTOR IS NOT
 SIGNEDON APPLICATION.
  
 9.BUILDING VALUATION IS TOO LOW BASED
 UPON SBCCI BUILDING VALUATION TABLES.
 VALUATION HAS BEEN REVISED TO $292,864
 ADDITIONAL PERMIT FEES ARE DUE.SEE FEE
 DETAIL ON APPLICATION.
  
 10.KD WINDOWS NOT LISTED ON THE DCA
 PRODUCT APPROVAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 11.SHEET A-2 NOTE REFER TO FBD CODE
 SECTIONS.CODE SHOULD BE FBC "FLORIDA
 BUILDING CODE".
  
 12.ENERGY CALCS NOT FOR CORRECT
 PROPERTY.SUBMIT NEW ENERGY CALCS.
  
 13.SOIL TEST SUBMITTED FOR WRONG
 PROPERTY.SUBMIT NEW SOIL TESTS.
  
 14.SURVEY AND SITE PLAN DO NOT MATCH.
 SUBMIT TWO COPIES OF A NEW SURVEY.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672