2004-04-15 00:00:00 | DENIED |
| |
| 1. THE NOTICE OF COMMENCEMENT SHALL BE |
| RECORDED AT PALM BEACH COUNTY |
| COURTHOUSEAND A COPY SUBMITTED TO THIS |
| OFFICE |
| BEFORE A PERMIT CAN BE ISSUED.BLANK |
| FORMS ARE AVAILABLE FROM THIS OFFICE. |
| |
| 2. BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 3.FBC 11-4.23.2 EXCEPTIONSAT LEAST |
| ONE BATHROOM DOOR SHALL HAVE A 29 INCH |
| CLEAR OPENING. |
| |
| 4.GENERAL ARCH. NOTES #8ALL WINDOWS |
| ARE TO BE IMPACT RESISTANT.THIS |
| CONFLICTS WITH OTHER NOTES OF |
| IMPACT PROTECTION REQUIRED. |
| |
| 5.SUBMIT MANUFACTURER SPECIFICATIONS |
| AND UL LISTING INFORMATION FOR GAS |
| BBQ AND HOOD. |
| |
| 6.SUBMIT 2 COPIES OF PRODUCT APPROVAL |
| FOR 1 HR GLASS BLOCK. |
| |
| 7.BUTT GLASS NOT USED.REMOVE |
| PRODUCT APPROVAL FROM THIS APPLICATION. |
| |
| 8.REMOVE ROOFING PRODUCT APPROVALS |
| A SEPERATE ROOFING PERMIT IS REQUIRED |
| SINCE A ROOFING CONTRACTOR IS NOT |
| SIGNEDON APPLICATION. |
| |
| 9.BUILDING VALUATION IS TOO LOW BASED |
| UPON SBCCI BUILDING VALUATION TABLES. |
| VALUATION HAS BEEN REVISED TO $292,864 |
| ADDITIONAL PERMIT FEES ARE DUE.SEE FEE |
| DETAIL ON APPLICATION. |
| |
| 10.KD WINDOWS NOT LISTED ON THE DCA |
| PRODUCT APPROVAL SITE. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATIONPLEASE SEE THE STATE WEBSITE |
| AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 11.SHEET A-2 NOTE REFER TO FBD CODE |
| SECTIONS.CODE SHOULD BE FBC "FLORIDA |
| BUILDING CODE". |
| |
| 12.ENERGY CALCS NOT FOR CORRECT |
| PROPERTY.SUBMIT NEW ENERGY CALCS. |
| |
| 13.SOIL TEST SUBMITTED FOR WRONG |
| PROPERTY.SUBMIT NEW SOIL TESTS. |
| |
| 14.SURVEY AND SITE PLAN DO NOT MATCH. |
| SUBMIT TWO COPIES OF A NEW SURVEY. |
| |
| ANY QUESTIONS CALL ME. |
| |
| ART LANGE |
| BUILDING PLANS EXAMINER |
| 805-6672 |