Plan Review Notes For Permit 04030145 |
Permit Number |
04030145 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-03-05 00:00:00 | DENIED | | REFERENCE: FBC-2001 FUEL GAS | | FBC-2001 CHAPTER 1 | | | | A) THE FOLLOWING INFORMATION REQUIRED | | FOR THE GAS REVISION: | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED) | | 3. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | THRU 402.5.2 AND TABLES 402(1) THRU | | 402(34). | | 4. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES (A)(3). | | 5) EXHAUST TERMINATION FOR GENERATOR. | | 6) ALL DRAWINGS SHALL BEAR THE NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | THE DESIGN. SECTION 104.2.1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|