Plan Review Notes For Permit 04030144 |
Permit Number |
04030144 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2006-04-25 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE SERVICE EQUIPMENT , A METER WITH | | A MAIN DISCONNECT MOUNTED NEXT TO IT, | | SHOWN ON THE RISER DO NOT MATCH THE | | METER ONLY SHOWN ON THE PLAN. PLEASE | | INDICATE ON BOTH ACTUAL CONDITIONS. | | | | 2} ON PANEL SCHEDULE "A" THE OCP FOR | | PANEL "B" IS 100 AMPS. ON THE RISER IT"S | | 50 AMPS, PLEASE CORRELATE. | | | | 3} THE POOL EQUIPMENT NOW HAS BEEN MOVED | | SINCE THE LAST REVISION, AND THE A/C | | DISCONNECTS WOULD APPEAR NOT TO HEVRE | | REQUIRED CLEARANCE PER 110.26. PLEASE | | FIELD VERIFY AND INDICATE CORRECT | | LOCATION ON PLAN. | | | | PLEASE VERIFY FIELD CONDITIONS WITH PLAN | | REVISION PRIOR TO RESUBMITTING FOR | | REVIEW. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/805-6731 | | | | | | |
|