2006-04-25 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE SERVICE EQUIPMENT , A METER WITH
 A MAIN DISCONNECT MOUNTED NEXT TO IT,
 SHOWN ON THE RISER DO NOT MATCH THE
 METER ONLY SHOWN ON THE PLAN. PLEASE
 INDICATE ON BOTH ACTUAL CONDITIONS.
  
 2} ON PANEL SCHEDULE "A" THE OCP FOR
 PANEL "B" IS 100 AMPS. ON THE RISER IT"S
 50 AMPS, PLEASE CORRELATE.
  
 3} THE POOL EQUIPMENT NOW HAS BEEN MOVED
 SINCE THE LAST REVISION, AND THE A/C
 DISCONNECTS WOULD APPEAR NOT TO HEVRE
 REQUIRED CLEARANCE PER 110.26. PLEASE
 FIELD VERIFY AND INDICATE CORRECT
 LOCATION ON PLAN.
  
 PLEASE VERIFY FIELD CONDITIONS WITH PLAN
 REVISION PRIOR TO RESUBMITTING FOR
 REVIEW.
  