2004-03-19 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} BOTH PANELS ON THE RISER ARE |
| DESIGNATED AS "A". |
| |
| 2} THE RISER DIAGRAM INDICATES #3/0 |
| FEEDERS TO THE SUB PANEL, THE PANEL |
| SCHEDULE INDICATES #3 FEEDERS, PLEASE |
| CORRELATE. |
| |
| 3} INDICATE THE LOCATION OF THE SERVICE |
| EQUIPMENT ON THE PLAN. |
| |
| 4} THE DISCONNECT LOCATION FOR THE |
| CONDENSER UNITS ARE IN VIOLATION OF |
| 110.26. |
| |
| 5} NOTE #9 REFERS TO ALL CONDUCTORS |
| BEING A MINIMUM OF #12, THERE ARE #14'S |
| ON THE PANEL SCHEDULE, PLEASE |
| CORRRELATE. |
| |
| 6} A SMOKE DETECTOR NEEDS TO BE ADDED |
| OUTSIDE THE GUEST BEDROOM PER |
| 8-1.4.1.6.2(2), "IMMEDIATE VICINITY". |
| |
| 7} ONLY THE RECEPTACLES IN THE BEDROOMS |
| ARE MARKED AS BEING ARC FAULT |
| PROTECTED,NOTE THAT ALL OUTLETS MUST BE |
| PER |
| 210.12, LIGHTS, SMOKE DETECTORS, FANS. |
| |
| 8} A RECEPTACLE MUST BE ADDED ON THE |
| KITCHEN COUNTER PER 210.52(C)(1). |
| |
| 9} A RECEPTACLE PER 210.52(A)(1) MUST |
| BE ADDED IN THE BREAKFAST ROOM. |
| |
| 10} THERE ARE TWO BEDROOMS LABELED #3 ON |
| SHEET E-1.(GUEST BEDROOM). |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |