2005-01-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA STATUTES
  
 A) FROM THE PREVIOUS REVIEW:
 BATH #3 TUB IS NOT VENTED. 902.1
 BATH #2 SHOWER IS NOT VENTED. 902.1
 MASTER BATH SHOWER REQUIRES A TRAP.
 1002.1
 B) NEW SHEETS REQUIRED FOR P-1 AND P-2
 SHOWING ALL CHANGES. HAND DRAWN
 CORRECTIONS ON THE PLANS ARE NOT
 ACCEPTABLE. SECTION 104.2.1.3.
 C) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 552.80(2)(B)
  
  