Plan Review Notes
Plan Review Notes For Permit 04030137
Permit Number 04030137
Review Stop P
Sequence Number 3
Notes
Date Text
2004-12-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-2 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. SECTION
 104.2.1.
 A) WASH MACHINE IS NOT VENTED. SECTION
 901.2.1.
 B)BATH #3 TUB IS NOT VENTED AND
 REQUIRES A TRAP. SECTIONS 901.2.1 AND
 1002.1.
 C) BATH #2 IS LABELED AS BATH #3 AND
 THE TUB IS NOT VENTED AND REQUIRES A
 TRAP. SECTIONS 901.2.1 AND 1002.1.
 D) MASTER BATH BIDET NOT VENTED AND
 REQUIRES A TRAP. SECTIONS 901.2.1 AND
 1002.1.
 2) SEE EXAMPLE OF A SANT. RISER DIAGRAM
 THAT WILL MEET THE CODE REQUIREMENTS ON
 ATTACHED SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]