2004-11-24 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 SECTION 1 | | | | 1) SHT P-1 SANITARY RISER DIAGRAM DOES | | NOT MEET CODE REQUIREMENTS, NOR DOES IT | | REFLECT THE FLOOR PLAN. | | A) BATH #3 TUB NOT VENTED, AND A TRAP | | IS REQUIRED. SECTIONS 902.1 & 1002.1 | | B) WASH MACHINE AS SHOWN IS AN "S' TRAP | | AND IS NOT APPROVED. A VENT IS REQUIRED | | AS WELL AS A STANDPIPE AND A CLEANOUT 4 | | FEET ABOVE THE FLOOR ON THE W/M STACK. | | SECTION 708.10, 902.1, 1002.1, & | | 1002.3(5) | | C) WET BAR SINK IS NOT VENTED AND PIPED | | AS SHOWN IS AN "S" TRAP WHICH IS NOT | | APPROVED. SECTION 902.1 & 1002.3(5). | | D) TRAP REQUIRED FOR SHOWER IN MASTER | | BATH, AND BIDET SHOWN ON THE FLOOR PLAN | | IS NOT ON THE RISER DIAGRAM. SECTIONS | | 1002.1 & 1104.2.1. | | E) SHOWER IN GUEST BATH IS NOT VENTED, | | AND REQUIRES A TRAP. SECTIONS 902.1 & | | 1002.1 | | F) INFORMATIONAL: IF KITCHEN SINK IS AN | | ISLAND SINK, THEN AN AIR ADMITTENCE | | VALVE MAY BE USED IF A VENT THROUGH THE | | ROOF CAN NOT BE INSTALLED. SECTION 917 | | | | | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|