Plan Review Notes
Plan Review Notes For Permit 04030137
Permit Number 04030137
Review Stop P
Sequence Number 2
Notes
Date Text
2004-11-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 SECTION 1
  
 1) SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLAN.
 A) BATH #3 TUB NOT VENTED, AND A TRAP
 IS REQUIRED. SECTIONS 902.1 & 1002.1
 B) WASH MACHINE AS SHOWN IS AN "S' TRAP
 AND IS NOT APPROVED. A VENT IS REQUIRED
 AS WELL AS A STANDPIPE AND A CLEANOUT 4
 FEET ABOVE THE FLOOR ON THE W/M STACK.
 SECTION 708.10, 902.1, 1002.1, &
 1002.3(5)
 C) WET BAR SINK IS NOT VENTED AND PIPED
 AS SHOWN IS AN "S" TRAP WHICH IS NOT
 APPROVED. SECTION 902.1 & 1002.3(5).
 D) TRAP REQUIRED FOR SHOWER IN MASTER
 BATH, AND BIDET SHOWN ON THE FLOOR PLAN
 IS NOT ON THE RISER DIAGRAM. SECTIONS
 1002.1 & 1104.2.1.
 E) SHOWER IN GUEST BATH IS NOT VENTED,
 AND REQUIRES A TRAP. SECTIONS 902.1 &
 1002.1
 F) INFORMATIONAL: IF KITCHEN SINK IS AN
 ISLAND SINK, THEN AN AIR ADMITTENCE
 VALVE MAY BE USED IF A VENT THROUGH THE
 ROOF CAN NOT BE INSTALLED. SECTION 917
  
  
  
 REVIEW BY KEN STEVENS