2004-11-22 00:00:00 | DENIED: | | 1.RETURN AIR NOT INDICATED FOR THE | | DEN/STUDY AREA. | | | | 2.RETURN AIR FROM AHU-2; TWO BRANCH | | LINES INDICATED FROM THE RETURN, BUT | | SHOW A SUPPLY SYMBOL. | | | | 3.RETURN AIR IS INDICATED FROM THE | | LINEN CLOSET.IS THIS CORRECT? | | | | 4.SEER INDICATED ON THE PLAN IS A 12 | | SEER RATING.ACCORDING TO THE ENERGY | | CALCULATIONS THE SEER SHALL BE A MINIMUM | | OF 13 SEER. | | | | 5.NOTE 21 ON PLAN SHEET M-1 INDICATES | | ONLY A 10.5 SEER MINIMUM.THE SEER CAN | | NOT BE LESS THAN THE ENERGY CALCS | | REQUIRE. | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | |
|