Plan Review Notes
Plan Review Notes For Permit 04030137
Permit Number 04030137
Review Stop M
Sequence Number 2
Notes
Date Text
2004-11-22 00:00:00DENIED:
 1.RETURN AIR NOT INDICATED FOR THE
 DEN/STUDY AREA.
  
 2.RETURN AIR FROM AHU-2; TWO BRANCH
 LINES INDICATED FROM THE RETURN, BUT
 SHOW A SUPPLY SYMBOL.
  
 3.RETURN AIR IS INDICATED FROM THE
 LINEN CLOSET.IS THIS CORRECT?
  
 4.SEER INDICATED ON THE PLAN IS A 12
 SEER RATING.ACCORDING TO THE ENERGY
 CALCULATIONS THE SEER SHALL BE A MINIMUM
 OF 13 SEER.
  
 5.NOTE 21 ON PLAN SHEET M-1 INDICATES
 ONLY A 10.5 SEER MINIMUM.THE SEER CAN
 NOT BE LESS THAN THE ENERGY CALCS
 REQUIRE.
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  