2004-04-13 00:00:00 | DENIED |
| 1. THE NOTICE OF COMMENCEMENT SHALL BE |
| RECORDED AT PALM BEACH COUNTY |
| COURTHOUSEAND A COPY SUBMITTED TO THIS |
| OFFICE |
| BEFORE A PERMIT CAN BE ISSUED.BLANK |
| FORMS ARE AVAILABLE FROM THIS OFFICE. |
| |
| 2.BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 3. BASED UPON SBCCI BUILDING VALUATION |
| DATA, PROJECT EVALUATION OF $220,000 IS |
| TO LOW AND THE REVISED VALUATION IS |
| $297,419.ADDITIONAL PERMIT FEES OF |
| $781.91 ARE DUE.104.6.5 WEST PALM |
| BEACH AMMENDMENT TO THE FBC. |
| |
| 4.WHAT ROOF TILE ARE YOU USING? |
| TWO DIFFERENT PRODUCT APPROVALS HAVE |
| BEEN SUBMITTED. SPANISH "S" IS |
| SPECIFIED ON PLAN. |
| |
| 5.PRODUCT APPROVAL FOR K.D> WINDOWS |
| ARE NOT LISTED ON THE DCA PRODUCT |
| APPROVAL SITE. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE |
| AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 6.SEPERATE ROOFING PERMIT REQUIRED. |
| CONTRACTOR NOT SIGNED ON AT TIME OF |
| APPLICATION. |
| |
| 7.SURVEY AND SITE PLAN DON'T MATCH. |
| |
| 8.PRODUCT APPROVALS FOR GLASS BLOCK |
| ARE MISSING. SUBMIT 2 COPIES. |
| |
| 9.TOTAL GROSS AREA LISTED ON PLAN IS |
| NOT CORRECT. |
| |
| 10.PAGE A-2 CHECK NOTES TO YOU MEAN |
| FBC, NOT FBD?CLARIFY |
| |
| 11.GEN ARCH. NOTES # 8 ALL WINDOWS |
| ARE TO BE IMPACT RESISTANT. PLEASE |
| CLARIFYSINCE IMPACT PROTECTION IS ALSO |
| SPEC'D OUT IN OTHER LOCATIONS. |
| |
| 12.GARDEN COURT:TABLE 600 |
| CALCULATIONS NOT ACCURATE. |
| TOTAL AREA 318 SQ. FT. X 20% = 63SQ.FT. |
| ALLOWABLE OPENINGS.ACTUAL OPENINGS |
| ARE 91.25 SQ. FT..PLEASE CHANGE AREA |
| TO COMPLY WITH TABLE 600 ALLOWABLE |
| OPENINGS. |
| |
| ART LANGE |
| BUILDING PLANS EXAMINER |
| 805-6672 |