Plan Review Notes
Plan Review Notes For Permit 04030137
Permit Number 04030137
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-13 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. BASED UPON SBCCI BUILDING VALUATION
 DATA, PROJECT EVALUATION OF $220,000 IS
 TO LOW AND THE REVISED VALUATION IS
 $297,419.ADDITIONAL PERMIT FEES OF
 $781.91 ARE DUE.104.6.5 WEST PALM
 BEACH AMMENDMENT TO THE FBC.
  
 4.WHAT ROOF TILE ARE YOU USING?
 TWO DIFFERENT PRODUCT APPROVALS HAVE
 BEEN SUBMITTED. SPANISH "S" IS
 SPECIFIED ON PLAN.
  
 5.PRODUCT APPROVAL FOR K.D> WINDOWS
 ARE NOT LISTED ON THE DCA PRODUCT
 APPROVAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SEPERATE ROOFING PERMIT REQUIRED.
 CONTRACTOR NOT SIGNED ON AT TIME OF
 APPLICATION.
  
 7.SURVEY AND SITE PLAN DON'T MATCH.
  
 8.PRODUCT APPROVALS FOR GLASS BLOCK
 ARE MISSING. SUBMIT 2 COPIES.
  
 9.TOTAL GROSS AREA LISTED ON PLAN IS
 NOT CORRECT.
  
 10.PAGE A-2 CHECK NOTES TO YOU MEAN
 FBC, NOT FBD?CLARIFY
  
 11.GEN ARCH. NOTES # 8 ALL WINDOWS
 ARE TO BE IMPACT RESISTANT. PLEASE
 CLARIFYSINCE IMPACT PROTECTION IS ALSO
 SPEC'D OUT IN OTHER LOCATIONS.
  
 12.GARDEN COURT:TABLE 600
 CALCULATIONS NOT ACCURATE.
 TOTAL AREA 318 SQ. FT. X 20% = 63SQ.FT.
 ALLOWABLE OPENINGS.ACTUAL OPENINGS
 ARE 91.25 SQ. FT..PLEASE CHANGE AREA
 TO COMPLY WITH TABLE 600 ALLOWABLE
 OPENINGS.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672