Plan Review Notes
Plan Review Notes For Permit 04030121
Permit Number 04030121
Review Stop M
Sequence Number 1
Notes
Date Text
2004-03-25 00:00:00DENIED:
 1.PLEASE PROVIDE INFORMATION ON WHAT
 WILL BE STORED IN THIS SPACE.
  
 2.PER 2001 FBC(M) TABLE 403.3, A
 MINIMUM OF .05 CFM PER SQ FT OF OUTSIDE
 AIR IS REQUIRED.INDICATE HOW THIS
 WILL BE ACHIEVED.PROVIDE OUTSIDE AIR
 CALCS.
  
 3.PLEASE PROVIDE MANUFACTURER
 INFORMATION ON THE "MINI-MATE" INDICATED
 ON THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.