1 |
|
Notes |
Date |
Text |
2004-03-25 00:00:00 | DENIED: | | 1.PLEASE PROVIDE INFORMATION ON WHAT | | WILL BE STORED IN THIS SPACE. | | | | 2.PER 2001 FBC(M) TABLE 403.3, A | | MINIMUM OF .05 CFM PER SQ FT OF OUTSIDE | | AIR IS REQUIRED.INDICATE HOW THIS | | WILL BE ACHIEVED.PROVIDE OUTSIDE AIR | | CALCS. | | | | 3.PLEASE PROVIDE MANUFACTURER | | INFORMATION ON THE "MINI-MATE" INDICATED | | ON THE PLAN. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|