Plan Review Notes For Permit 04030098 |
Permit Number |
04030098 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-04-13 00:00:00 | ********** NOTES/ PROVISO *********** | | | | 1)NOTE: PLEASE SEE LOAD CALCULATIONS, | | PLEASE CORRELATE LOADS FOR PANELS "K" & | | "P" TO T-1. PLEASE ADJUST FINAL LOADS | | FOR PANELS "A" ETC. | | | | PLEASE SUBMIT THE ABOVE CHANGES AND ANY | | OTHER REVISIONS BEFORE ROUGH ELECTRICAL | | INSPECTION IS CALLED IN. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|