Plan Review Notes
Plan Review Notes For Permit 04030098
Permit Number 04030098
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-09 00:00:00**** UNSAT ****
  
 1)NOTE: PLEASE SEE FIRE REVIEW AS THEY
 WILL HAVE AN AFFECT ONELECTRICAL PLANS.
  
 2)NOTE: PLEASE CLARIFY SIZE AND # OF
 CONDUCTORS ON SECONDARY SIDE OF TRANS-
 -FORMER. SHOWS 3-1/0'S, NEUTRAL?
 PLEASE CLARIFY WHAT WILL LIMIT THE LOAD
 ON LOAD SIDE OF X-FORMER FOR RATING OF
 1/0'S? PLEASE SEE 240.21 FOR TAPPED
 CONDUCTORS.
  
 3)NOTE: PLEASE CLARIFY TYPE OF EM LTS
 BEING USED. ELETRICAL LEGEND MENTIONS
 FLOURESCENT FIXTURES BEING WIRED TO AN
 EMERGENCY CIRCUIT.? PLEASE CLARIFY
 PLANS DO NOT SEEM TO INDICATE AN EM
 PANEL OR EM SOURCE?
 PLEASE SEE 700.12,700.12E .
  
 4)NOTE: PLEASE CLARIFY CONTINUOUS LOADS
 AT 125%. 215.3,230.42 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]