Plan Review Notes For Permit 04030098 |
Permit Number |
04030098 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-03-09 00:00:00 | **** UNSAT **** | | | | 1)NOTE: PLEASE SEE FIRE REVIEW AS THEY | | WILL HAVE AN AFFECT ONELECTRICAL PLANS. | | | | 2)NOTE: PLEASE CLARIFY SIZE AND # OF | | CONDUCTORS ON SECONDARY SIDE OF TRANS- | | -FORMER. SHOWS 3-1/0'S, NEUTRAL? | | PLEASE CLARIFY WHAT WILL LIMIT THE LOAD | | ON LOAD SIDE OF X-FORMER FOR RATING OF | | 1/0'S? PLEASE SEE 240.21 FOR TAPPED | | CONDUCTORS. | | | | 3)NOTE: PLEASE CLARIFY TYPE OF EM LTS | | BEING USED. ELETRICAL LEGEND MENTIONS | | FLOURESCENT FIXTURES BEING WIRED TO AN | | EMERGENCY CIRCUIT.? PLEASE CLARIFY | | PLANS DO NOT SEEM TO INDICATE AN EM | | PANEL OR EM SOURCE? | | PLEASE SEE 700.12,700.12E . | | | | 4)NOTE: PLEASE CLARIFY CONTINUOUS LOADS | | AT 125%. 215.3,230.42 ETC | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|