Plan Review Notes
Plan Review Notes For Permit 04030037
Permit Number 04030037
Review Stop M
Sequence Number 2
Notes
Date Text
2004-08-12 00:00:00DENIED:2ND REVIEW
 REFERENCE REVIEW DATED 3-29-04
 COMMENT #1, REQUEST FOR THE BUILDING
 CONSTRUCTION TYPE.PLANS SHEET M-3
 REVISION NOTE INDICATES THE BUILDING
 TYPE WAS IDENTIFIED ON PLAN SHEET A-5.
 A-5 DOES NOT INDICATE BUILDING
 CONSTRUCTION TYPE.
  
 COMMENT #3, REQUEST FOR UL LISTING FOR
 THE WOOD FLOOR/CEILING ASSEMBLY WAS NOT
 ADDRESSED.
  
 COMMENT #4, OUTSIDE AIR CALCULATIONS
 WERE PROVIDED BUT THE FLOOR PLAN DOES
 NOT INDICATE OUTSIDE AIR INTAKE, LAYOUT
 OR DUCT SIZE AND MATERIAL.
  
 NEW COMMENT - PLAN SHEET M-3 DETAIL OF
 THE AIR HANDLING UNIT MOUNTING.DETAIL
 INDICATES 4" DRYER DUCT TERMINATING
 UNDER THE RETURN TO THE AHU.SHOULD
 THIS READ OUTSIDE AIR DUCT?PLEASE
 CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.