Plan Review Notes
Plan Review Notes For Permit 04030026
Permit Number 04030026
Review Stop B
Sequence Number 1
Notes
Date Text
2004-04-06 00:00:00BUILDING PLAN REVIEW
 PERMIT# 04030026
 ADD: 351 WENONAH PLACE
 CONT: KOMAKO CONSTRUCTION
 TEL: (305)332-7174
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) NOTICE OF COMMENCEMENT REQUIRED BE-
 FORE ISSUANCE OF PERMIT.
  
 2) PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT:
 FL STATE STAT: 61G15.23.002 ENGINEERS
 FL STATE STAT: 61G16.003 ARCHITECTS
 ARCHITECT BUSINESS LICENSE- DELINQENT
 3) 1804.2.2 QUESTIONABLE SOILS, WHERE
 THE MINIMUM SAFE BEARING CAPACITY IS
 NOT KNOWN OR IS QUESTION, SUBMIT REPORT
 BY TRIANGLE TESTING LAB.
  
 4) BEFORE A PERMIT TO CONSTRUCT, OR
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET
 OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 5) PLANS DO NOT SHOW TOWNHOUSES SEPERA-
 TION, SEE 704.4.1 INDICATE COMPLIANCE
 WITH SUBSECTIONS 1-3. TOWNHOUSES NOT
 MORE THAN 3 STORIES IN HEIGHT MAY BE
 SEPERATION BY A SINGLE WALL MEETING THE
 SUB-REQUIREMENTS 1-3.
  
 6) EGRESS WINDOWS (2ND FLOOR) PROVIDE
 THE MANUFACTURERS CUT SHEETS WITH
 NET CLEAR OPENING SIZES MINIMUM OF
 5.7 SQ FT.
  
 7) FBC 1005.4.5 (GLITCH AMENDMENT)
 JULY1,2003 REQUIRES AT LEAST ONE MEANS
 OF ESCAPE FROM A DWELLING WHEN SHUTTERED
 FOR IMPACT PROTECTION. THE MEANS OF
 ESCAPE SHALL BE WITHIN THE FIRST FLOOR
 OF THE DWELLING & CAN NOT BE LOCATED IN
 A GARAGE. OCCUPANTS IN ANY PART OF THE
 DWELLING SHALL HAVE ACCESS TO IT WITHOUT
 HAVING TO PASS THROUGH A LOCK ABLE DOOR
 NOT UNDER THEIR CONTROL. INDICATE HOW
 COMPLIANCE WILL BE ACHEIVED.
  
 8) PROVIDE INFORMATION ALSO IN REGUARDS
 TO 2ND STORY WINDOWS. EITHER LARGE
 MISSLE IMPACT RESISTANT OR STORM SHUT-
 TERS THAT CAN BE INSTALLED ON THE EXTER-
 IOR BUT THROUGH THE WINDOW OPENING.NOTE
 NO GARAGE FOR THE STORAGE OF LADDERS!
  
 9) 1606.1.7 FL BLDG CODE THE FOLLOWING
 INFORMATION IS REQUIRED RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 A) BASIC WIND SPEED
 B) WIND IMPORTANCE FACTOR & BUILDING
 CATEGORY
 C) WIND EXPOSURE
 D) INTERNAL PRESSURE COEFFICIENT
 E) COMPONENTS AND CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE POS/ NEG WALL/ OPENING
 PRESSURES, INTERIOR AND END ZONES.
  
 10) FL BLDG CODE 1606.1.5 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED AND OPERATABLE
 B) EXTERIOR DOORS SWING AND SLIDING
 C) MULLIONS IF ANY
 D) STORM SHUTTERS
 E) ROOF ASSEMBLY
 F) TRUSS ANCHORS CONCRETE/ WOOD/ WOOD
  
 11) IF WINDOWS ARE NOT LARGE MISSLE
 RESISTANT, THEN STORM SHUTTERS WIL BE
 REQUIRED. 2ND STORY WINDOWS SHALL RE-
 QUIRE SHUTTERS THAT CAN BE INSTALLED
 WITHOUT USE OF A LADDER!
  
 12) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS & MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.FBC 1606.1.4
  
 13) TABLE 600 UNITS 1-5 10'-20' ALLOW-
 ABLE OPENING AREA (40%) IS 69.31 SQ FT,
 UNITS 6-11 20'-30' ALOWABLE OPENING AREA
 IS 103.96 SQ FT. THE ACTUAL AREA OF OPEN
 ING FOR THE 2 SLIDERS IS 112SQ FT. THE
 TOTAL WALL AREA FOR THE FIRST FLOOR IS
 173.28 SQ FT.
  
 14) CORRECT SHEET A-3, A-4 SECTIONS
 2510.5,2510.5.11,& 2510.1.2.DELETE
 THESE NOTES WE ARE NOT LOCATED IN A
 HIGH VELOCITY HURRICANE ZONE!
  
 15)A-3, A-4, WINDERS, 1007.8.1:
 WINDERS SHALL HAVE A MINIMUM TREAD DEPTH
 OF 6" AT THE NARROWEST EDGE & SHALL
 HAVE A MINIMUM TREAD DEPTH OF 11" AT A
 POINT 12" FROM THE NARROW EDGE. WINDERS
 SHALL BE PERMITTED TO BE USED AS A COM-
 PONENT IN A MEANS OF EGRESS WITHIN A
 DWELLING UNIT.
  
 15) A-5 STAIRWAY/ GUARDRAIL TO CONFORM
 WITH 1015.3 (1) A 6" SPHERE SHALL NOT BE
 ABLE TO PASS THROUGH THE TRIANGULAR
 OPENING FORMED BY THE TREAD,RISER AND
 THE BOTTOM RAIL OF THE GUARDRAIL!
  
 16) 2305.2.2 FLOOR/ CEILING ASSEMBLIES/
 IN SINGLE FAMILY DWELLINGS FLOOR-CEILING
 ASSEMBLIES SEPERATING USABLE SPACE INTO
 2 OR MORE APPROXIMATE AREAS WITH NO AREA
 GREATER THAN 500 SQ FT. DRAFTSTOPING
 SHALL BE PROVIDED PARALLEL TO THE MAIN
 FRAMING MEMBERS.
  
 17) SHEET S-4:
 A) PROVIDE NAILING FOR ROOF SEE TABLE
 2306.1 PALM BEACH COUNTY AMENDMENTS.
 B) ROOF PLAN INDICATES THIS TO BE LOCAT
 ED IN A COASTAL ZONE, IN ACTUALLITY IT
 IS A "B" ZONE. IF CALCULATED ASA "C"
 THEN ALL WALL, ROOF AND OPENING PRES-
 SURES TO BE CALCULATED WITH THIS FACTOR.
 C) PROVIDE MEAN ROOF HEIGHT?
  
 18) S-5 PLANS INDICATE THE FOUNDATION
 TO BE RECESSED IN THE EARTH 8", 1804.1.3
 THE BOTTOM OF THE FOUNDATION SHALL
 EXTEND NO LESS THAN 12" BELOW FINISH
 GRADE.
  
 19) 1909.3 CONCRETE SLABS ON GRADE
 CONTAINING 6X6/10/10 WELDED WIRE REIN-
 FORCMENT FABRIC LOCATED IN THE MIDDLE TO
 THE UPPER 1/3RD OF THE SLAB SHALL BE
 SUPPORTED BY APPROVED MATERIALS OR SUP-
 PORTS AT SPACING NOT TO EXCEED 3 FT OR
 IN ACCORDANCE WITH MANUFACTURERS SPEC.
  
 20) 2309.6 ATTIC ACCESS, PROVIDE ATTIC
 ACCESS 20'X36".
  
 21) PROVIDE INFORMATION FOR VENTILATION
 OF ATTIC SPACE 2309.7 THE TOTAL NET FREE
 VENTILATING AREA TO THE AREA OF THE CEIL
 ING SHALL NOT BE LESS THAN 1/150.
  
 22) THROUGH OUT THE PLANS CODE ARTICLES
 ARE MENTIONED TO COMPLY WITH,
 104.2.1 WEST PALM BEACH ADMINISTRATIVE
 CODE, INFORMATION SHALL BE SPECIFIC, AND
 THE TECHNICAL CODES SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVANT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION.
 BUILDING PLAN REVIW
 JIM WITMER
 (561)805-6715