Plan Review Notes For Permit 04030025 |
Permit Number |
04030025 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-08-11 00:00:00 | DENIED:2ND REVIEW | | REFERENCE REVIEW DATED 3/29/04 | | COMMENT #1, REQUEST FOR BUILDING | | CONSTRUCTION TYPE.PLAN SHEET M-3 | | REVISION NOTE INDICATES THE BUILDING | | TYPE WAS IDENTIFIED ON PLAN SHEET A-5. | | A-5 DOES NOT INDICATE BUILDING TYPE. | | | | COMMENT #3, REQUEST FOR UL ASSEMBLY | | FOR THE WOOD FLOOR/CEILING ASSEBMLY WAS | | NOT ADDRESSED. | | | | COMMENT #4, OUTSIDE AIR CALCULATIONS | | WERE PROVIDED BUT THE PLAN FLOOR PLAN | | DOES NOT INDICATE OUTSIDE AIR INTAKE, | | LAYOUT OR DUCT SIZE AND MATERIAL. | | | | NEW COMMENT - PLAN SHEET M-3 DETAIL OF | | THE AIR HANDLING UNIT MOUNTING DETAIL | | INDICATES 4" DRYER EXHAUST TERMINATING | | UNDER THE RETURN AIR PLENUM.SHOULD | | THIS READ OUTSIDE AIR DUCT?PLEASE | | CLARIFY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|