Plan Review Notes
Plan Review Notes For Permit 04030025
Permit Number 04030025
Review Stop M
Sequence Number 2
Notes
Date Text
2004-08-11 00:00:00DENIED:2ND REVIEW
 REFERENCE REVIEW DATED 3/29/04
 COMMENT #1, REQUEST FOR BUILDING
 CONSTRUCTION TYPE.PLAN SHEET M-3
 REVISION NOTE INDICATES THE BUILDING
 TYPE WAS IDENTIFIED ON PLAN SHEET A-5.
 A-5 DOES NOT INDICATE BUILDING TYPE.
  
 COMMENT #3, REQUEST FOR UL ASSEMBLY
 FOR THE WOOD FLOOR/CEILING ASSEBMLY WAS
 NOT ADDRESSED.
  
 COMMENT #4, OUTSIDE AIR CALCULATIONS
 WERE PROVIDED BUT THE PLAN FLOOR PLAN
 DOES NOT INDICATE OUTSIDE AIR INTAKE,
 LAYOUT OR DUCT SIZE AND MATERIAL.
  
 NEW COMMENT - PLAN SHEET M-3 DETAIL OF
 THE AIR HANDLING UNIT MOUNTING DETAIL
 INDICATES 4" DRYER EXHAUST TERMINATING
 UNDER THE RETURN AIR PLENUM.SHOULD
 THIS READ OUTSIDE AIR DUCT?PLEASE
 CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.