2004-03-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHTS A-3 & A-4 SHOW LOCATION OF WASH
 MACHINE ON FLOOR PLAN EACH TYPE UNIT.
 SECTION 104.2.1.
 2) SHTS P-2 & P-4 (SANT. RISER) BIDET
 NOT VENTED. SECTION 901.2.1.
 3) SHT P-2 LAV IN MASTER BATH LABLED W/C
 AND 2ND LAV PIPING NOT SHOWN ON FLOOR
 PLAN FOR UNITS A & B. SECTION 104.2.1.
 4) SHTS P-4 & P-5 CLEANOUT FOR WASH
 MACHINE SHALL BE 4' AFF FOR ACCESS.
 SECTION 708.10.
 5) SHT P-5 DOMESTIC WATER ISOMETRIC, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 ISOMETRIC. WATER HAMMER ARRESTORS SHALL
 BE LOCATED AT THE REFRIG. AND DISH WASH-
 ER PER 604.9. ALL WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SOME ARE SHOWN. WH-PDI 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
  